E45-370 · Environmental Protection and Temperature/Humidity · Proximity Sensor · ★★
In the dry, dusty environment of a flour workshop, static charge builds up on the sensor housing and discharges, causing momentary signal jumps and a safety hazard
[Mechanism] Friction among dry dust particles builds static charge on the insulating housing; the potential rises until it breaks down and discharges, momentarily disturbing the signal loop.
[Calculation] In a dry environment the static potential on the housing can reach several kV; the discharge pulse couples into the signal line and causes a momentary jump.
[Design Deficiency] The insulating housing had no bleed-off path, and no anti-static or explosion-proof assessment was carried out.
① Anti-static housing: choose a conductive or antistatic housing → bleed off charge
② Reliable grounding: single-point ground the housing to bleed static → eliminate buildup
③ Surface dissipation: apply an antistatic coating to lower surface resistance → slow the buildup
④ Shielded signal line: shield and ground the signal line → resist discharge coupling
⑤ Humidity control: humidify the environment moderately to reduce static → lessen the buildup
⑥ Explosion-proof assessment: select the model by explosion-proof rating for dusty areas → ensure safety
⑦ Static verification: run an electrostatic discharge immunity test to confirm → data confirmation
⑧ Selection standardization: write the dust and static condition into the selection criteria → control at the source
GB/T 17626.2-2018 Electromagnetic compatibility - Testing and measurement techniques - Electrostatic discharge immunity test