E45-372 · Environmental Protection and Temperature/Humidity · Pressure Sensor · ★★★
At a seaside platform pressure transmitter, combined high salt fog and high humidity accelerate corrosion of the housing and terminals, causing water ingress, drift, and failure
[Mechanism] Salt-fog chloride ions and high humidity act together to accelerate electrochemical corrosion; pitting that lets water in and oxidized terminals together make the error surge.
[Calculation] Seaside salt fog plus 95%RH drives the carbon-steel corrosion rate to 10 times that of inland; within half a year it perforates and lets water in, causing a 2%FS out-of-tolerance.
[Design Deficiency] The corrosion resistance of the housing and terminals was inadequate, and no protection was designed for a marine atmosphere.
① Corrosion-resistant housing: choose a 316L or duplex-steel housing → salt-fog resistance
② Gold-plated terminals: gold-plate the terminals to resist chloride corrosion → maintain contact
③ Fully sealed potting: pot the terminal chamber to keep out salt fog → prevent water ingress
④ Heavy-duty coating: apply a marine-grade coating to the housing → slow corrosion
⑤ Positive-pressure protection: fill the enclosure with dry nitrogen at a slight positive pressure → block ingress
⑥ Regular inspection: patrol for corrosion points and treat them promptly → early detection
⑦ Salt-fog verification: run a long-cycle neutral salt-spray test to confirm → data confirmation
⑧ Selection standardization: write the marine-atmosphere service condition into the corrosion-protection selection criteria → control at the source
GB/T 2423.17-2008 Environmental testing for electric and electronic products - Salt mist test