E45-376 · Communication and Bus · Communication Module · ★★
The master and slave baud rates do not match, so communication cannot be established at all and polling gets no response
[Mechanism] Different baud rates at the two ends of an asynchronous serial link shift the sampling instant for each bit; frame synchronization is lost and the data cannot be parsed.
[Calculation] With the master at 9600 bps and the slave at 19200 bps, accumulated sampling error misreads the stop bit and the frame error rate is 100%.
[Design Deficiency] Master and slave parameters were not configured uniformly, and there was no configuration checklist to verify against.
① Uniform parameters: verify that master and slave baud rates match → establish communication
② Configuration checklist: list communication parameters in the commissioning checklist → prevent misconfiguration
③ DIP-switch fixing: fix the slave baud rate with hardware DIP switches → prevent wrong settings
④ Auto-negotiation: choose modules that support automatic baud detection → no misconfiguration
⑤ Power-up self-check: verify parameter consistency at power-up and alarm → early detection
⑥ Protocol scan: scan the actual baud rate with a protocol analyzer → locate the deviation
⑦ Configuration verification: read back parameters after communication is established → data confirmation
⑧ Selection standardization: write the baud rate into the interface spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification