E45-375 · Communication and Bus · Communication Module · ★★
No 120 Ω terminator resistors are fitted at the ends of the RS485 bus; long-distance communication suffers frequent bit errors and packet loss, with a bit error rate above 1%
[Mechanism] Impedance mismatch at the end of the transmission line reflects signals back and superimposes them; the received waveform is distorted and sampling goes wrong.
[Calculation] The 1200 m bus has a characteristic impedance of 120 Ω; with no terminator the reflection coefficient is ≈1, and the superimposed reflected wave closes the eye diagram and causes bit errors.
[Design Deficiency] Terminator resistors were omitted out of short-run habit, and line impedance matching was not budgeted.
① Terminator resistors: connect a 120 Ω terminator across each end of the bus → impedance matching
② Resistor position: keep terminator resistors right at the bus end of the farthest node → no stub
③ Topology optimization: use a hand-in-hand bus with no long branches → fewer reflections
④ Baud adaptation: lower the baud rate on long lines to match the distance → fewer bit errors
⑤ Bias resistors: add pull-up/pull-down bias to hold a defined idle state → prevent garbled data
⑥ Repeater extension: add RS485 repeaters beyond the distance limit → extend the range
⑦ Termination verification: check the waveform and eye diagram on an oscilloscope → data confirmation
⑧ Selection standardization: make terminator resistors mandatory for long-line communication → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification