E45-378 · Communication and Bus · Communication Module · ★★
Two slaves are set to the same Modbus address; when the master polls that address the returned data conflicts and is scrambled
[Mechanism] Slaves with the same address respond at the same time; bus contention causes message collisions and frame errors.
[Calculation] Duplicate addresses make both nodes respond in the same frame; superimposed CRCs raise the frame error rate seen by the master and cause misreads.
[Design Deficiency] Addresses are set manually and easily duplicated, with no uniqueness check.
① Unique addressing: assign addresses uniquely from a planning table → no conflicts
② Factory-set address: burn the address at the factory so it cannot be changed → prevent duplicates
③ Unique DIP setting: limit the DIP-switch range to prevent out-of-range values → enforce uniqueness
④ Power-up self-check: detect address conflicts at power-up and alarm → early detection
⑤ Scan check: scan online addresses before the master polls → find duplicates
⑥ Configuration records: keep address configuration records for traceability → prevent errors
⑦ Conflict verification: inspect conflict frames with a protocol analyzer → data confirmation
⑧ Selection standardization: write address uniqueness into the commissioning spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification