Problem Description

The communication shield is grounded at both ends; the ground potential difference drives a circulating current in the shield, and the superimposed noise causes bit errors

Root Cause

[Mechanism] The ground potential difference between two grounded points drives a circulating current in the shield, and the induced noise couples into the signal line.
[Calculation] A 5 V potential difference between the two ground points drives tens of mA through the shield; the induced noise exceeds the signal tolerance and causes bit errors.
[Design Deficiency] The shield was mistakenly grounded at both ends, without evaluating the ground potential difference.

Corrective Solution

① Single-end grounding: ground the shield at one end only → break the circulating current
② Grounding choice: ground at the signal-source end only → control potential
③ Isolated floating: use an isolated transceiver so the far end floats → no ground difference
④ Common-mode rejection: choose modules with a high common-mode rejection ratio → noise immunity
⑤ Potential equalization: add equipotential bonding between the two sites → reduce potential difference
⑥ Shield inspection: check the shield connection and change it to single-end → early correction
⑦ Circulating-current verification: measure the shield current and confirm it drops to zero → data confirmation
⑧ Selection standardization: write shield grounding into the wiring spec → control at the source