E45-382 · Communication and Bus · Communication Module · ★★
RS485 runs beyond 1200 m without a repeater; signal attenuation leaves far-end nodes unable to communicate
[Mechanism] Over long distances, signal attenuation and distributed capacitance grow, and the received amplitude falls below the threshold so no decision can be made.
[Calculation] Attenuation over 1200 m of twisted pair drops the signal amplitude below the threshold, and the bit error rate rises exponentially with distance.
[Design Deficiency] Distance and attenuation were not budgeted on short-run experience, and no repeater was added.
① Distance budgeting: keep the communication distance ≤ the standard 1200 m → keep reliability
② Repeater extension: add RS485 repeaters beyond that distance → extend the range
③ Lower baud rate: lower the baud rate over long distance to raise tolerance → fewer bit errors
④ Thicker conductor: choose low-attenuation communication cable → less loss
⑤ Termination: match terminator resistors at both ends → suppress reflections
⑥ Distance inspection: measure the actual distance at completion → early detection
⑦ Attenuation verification: test bit errors at the far end → data confirmation
⑧ Selection standardization: write the communication distance into the design criteria → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification