E45-384 · Communication and Bus · Communication Module · ★★
The master runs a different firmware protocol version than a new batch of slaves, so some function codes are unsupported and communication fails
[Mechanism] Protocol version differences change the frame format or the function code definitions, so the slave returns an exception code and communication breaks down.
[Calculation] A V1.0 master sends a function code added in V2.0; the slave returns illegal function code 01 and the request fails.
[Design Deficiency] Firmware versions were not managed centrally, and batches were mixed.
① Version alignment: align master and slave firmware versions → keep compatibility
② Version management: keep a version register and forbid mixing → control consistency
③ Compatibility design: have the slave support legacy function codes → bridge differences
④ Startup handshake: report versions to each other at power-up and alarm on mismatch → early detection
⑤ Degraded communication: have the master fall back to the slave's capabilities → keep it usable
⑥ Upgrade procedure: use one upgrade process and keep records → prevent errors
⑦ Version verification: read and check the version numbers → data confirmation
⑧ Selection standardization: write the protocol version into the interface spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification