E45-385 · Communication and Bus · Communication Module · ★★
Devices at the two ends of a long RS485 link have different ground potentials; the common-mode voltage exceeds the receiver tolerance, causing bit errors and occasional damage
[Mechanism] The difference in grounding resistance between the two sites puts a ground potential difference across the bus; that common-mode voltage exceeds the transceiver's common-mode range and causes bit errors.
[Calculation] The 10 V potential difference between the two ground points exceeds the typical ±7 V common-mode range; the receiver saturates, causing bit errors and accelerated aging.
[Design Deficiency] No isolated transceiver was used, and no equipotential bonding was done.
① Isolated transceiver: use a magnetically isolated transceiver → break the ground coupling
② Equipotential bonding: add an equipotential copper busbar between the sites → reduce potential difference
③ Single-end grounding: ground the shield at one end only → break ground loops
④ Common-mode selection: choose a ±15 V wide common-mode transceiver → added margin
⑤ Floating arrangement: leave the remote device floating, ungrounded → no ground difference
⑥ Potential monitoring: measure the potential difference between sites and alarm → early detection
⑦ Common-mode verification: apply a common-mode voltage and measure bit errors → data confirmation
⑧ Selection standardization: write the ground potential difference into the communication design criteria → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields