E45-386 · Communication and Bus · Communication Module · ★★★
The communication port is not isolated; field ground-potential transients (ground bounce) produce a transient common mode that breaks down the transceiver, permanently damaging the port
[Mechanism] A non-isolated transceiver connects directly to ground; a transient ground-potential shift (ground bounce) is injected through the interface and breaks down the internal devices.
[Calculation] The ground-bounce transient reaches tens of volts, exceeding the device withstand voltage; the transceiver's surge protection is insufficient and it breaks down.
[Design Deficiency] A transceiver with isolation and protection was not chosen.
① Isolated transceiver: choose a magnetically isolated transceiver → break ground bounce
② Port protection: add TVS diodes and a resettable fuse → suppress transients
③ Common-mode rejection: choose devices with a wide common-mode range → ground-bounce immunity
④ Separate supply: use an independent isolated supply on the isolated side → preserve isolation
⑤ Grounding optimization: bring the communication ground in at a single point → control potential
⑥ Protection inspection: check that port protection devices are intact → early detection
⑦ Immunity verification: run an EFT surge test → data confirmation
⑧ Selection standardization: write isolation and protection into the interface spec → control at the source
GB/T 17626.5-2019 Electromagnetic compatibility - Testing and measurement techniques - Surge immunity test