E45-387 · Communication and Bus · Communication Module · ★★
The master's communication timeout is set too short; any occasional slave delay triggers repeated reconnects, bus load spikes and even more packets are lost
[Mechanism] Too short a timeout threshold makes even an occasional single-frame delay look like a timeout; the master repeatedly retransmits and reconnects, filling the bus bandwidth.
[Calculation] The timeout is set to 50 ms while the slave occasionally takes 200 ms; reconnects push bus load from 30% to 90% in a vicious cycle.
[Design Deficiency] The timeout was set on ideal assumptions with no margin.
① Timeout with margin: set timeout ≥3× the maximum response → prevent false timeouts
② Retransmission limit: cap retransmission attempts to avoid a storm → control load
③ Backoff: back off and retry after failures → reduce impact
④ Response optimization: speed up slave processing to cut latency → fewer timeouts
⑤ Load monitoring: monitor bus load and alarm → early detection
⑥ Parameter tuning: tune the timeout to the measured response → match reality
⑦ Storm verification: inject delay and test reconnect behavior → data confirmation
⑧ Selection standardization: write timeout parameters into the communication spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification