E45-391 · Communication and Bus · Communication Module · ★★
Outdoor bus connectors oxidize over time; rising contact resistance makes the bit error rate climb with humidity
[Mechanism] Oxidation of the connector metal forms an oxide layer that raises contact resistance; the voltage drop in the signal loop grows and level decisions go wrong.
[Calculation] Connector oxidation raises contact resistance from 10 mΩ to 2 Ω; the voltage drop reduces signal amplitude and the bit error rate rises.
[Design Deficiency] The connectors were not treated against oxidation and were not sealed.
① Gold-plated terminals: choose gold-plated, oxidation-resistant connectors → keep contact
② Sealed connectors: use IP67 sealed connectors → block moisture
③ Anti-oxidation grease: apply anti-oxidation conductive grease to contacts → slow oxidation
④ Reliable crimping: use crimped connections instead of screw terminals → stable contact
⑤ Regular maintenance: inspect connectors and clean oxidation → early detection
⑥ Contact monitoring: monitor the bit error trend and alarm → early correction
⑦ Oxidation verification: age in hot humid conditions and measure resistance → data confirmation
⑧ Selection standardization: write connector protection into the wiring spec → control at the source
GB/T 2423.4-2008 Environmental testing for electric and electronic products - Damp heat, cyclic test