E45-392 · Communication and Bus · Communication Module · ★★★
An outdoor overhead bus takes an induced lightning surge; the transceivers at the communication ports break down and are damaged in batches
[Mechanism] Lightning induces a kilovolt-level surge on the long line; injected through the interface, it breaks down the transceiver and protective devices.
[Calculation] The induced surge reaches 2 kV and exceeds the device withstand voltage; with no protection the transceiver is broken down by the surge and damaged.
[Design Deficiency] No surge protection or isolation was fitted on the outdoor bus.
① Surge protection: add TVS diodes and gas discharge tubes at the port → discharge the surge
② Isolated transceiver: use an isolated transceiver to break the ground coupling → common-mode immunity
③ Shield grounding: ground the shield at one end only to divert current → conduct lightning current away
④ Lightning-safe routing: route cables clear of high-risk lightning paths → less induction
⑤ Equipotential bonding: bond equipment to a common ground → reduce potential difference
⑥ Protection inspection: check that protective devices are intact → early detection
⑦ Surge verification: run a surge immunity test → data confirmation
⑧ Selection standardization: write lightning protection into the outdoor spec → control at the source
GB/T 17626.5-2019 Electromagnetic compatibility - Testing and measurement techniques - Surge immunity test