With many nodes on a bus-powered line, the supply voltage at the end node drops, causing repeated resets
[Mechanism] Bus supply current accumulates voltage drop across the line resistance, so the end-node voltage falls below the undervoltage threshold and the node resets repeatedly.
[Calculation] The bus powers 10 nodes at a total current of 0.5 A; with 2 Ω line resistance the end drop is 1 V, falling from 24 V to 23 V, close to the reset threshold.
[Design Deficiency] The line resistance × current and the voltage-drop margin were not budgeted.
① Larger conductor: choose a larger cross-section supply wire to cut line resistance → less voltage drop
② Node current limiting: limit per-node power consumption → lower total current
③ Segmented supply: supply long lines locally in segments → compensate the drop
④ Voltage monitoring: alarm on undervoltage at end nodes → early detection
⑤ Margin budgeting: keep voltage drop ≤5% of rated → keep reliability
⑥ Voltage boost compensation: use regulation to compensate the end-node voltage → stable supply
⑦ Drop verification: measure end-node voltage at full load → data confirmation
⑧ Selection standardization: write bus-supply margin into the design criteria → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification