E45-394 · Communication and Bus · Communication Module · ★★
RS485 is wired in a star topology; reflections at the center node are severe and communication with far-end nodes is unstable
[Mechanism] Whether star-topology branches are equal in length or not, they produce multiple reflections that superimpose and degrade signal quality, causing bit errors.
[Calculation] The reflection coefficient at the star center is high, and reflections from multiple branches superimpose to close the eye diagram and raise the bit error rate.
[Design Deficiency] A star topology was used mistakenly, without conversion to a daisy chain or the addition of a hub.
① Daisy chain: change to a hand-in-hand daisy-chain topology → suppress reflections
② Hub: use an RS485 hub to convert the star → isolate branch segments
③ Termination: add terminator resistors at each trunk end → control impedance
④ Short stubs: if branches are unavoidable, keep them <0.3 m → reduce reflections
⑤ Repeater isolation: isolate each branch through a repeater → no mutual interference
⑥ Topology inspection: check the topology and fix star wiring at completion → early correction
⑦ Reflection verification: check waveform and eye diagram on an oscilloscope → data confirmation
⑧ Selection standardization: write bus topology into the wiring spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification