E45-395 · Communication and Bus · Communication Module · ★★
RS485 runs a long line at the high baud rate of 115200 bps; the bit error rate rises with distance until it becomes unusable
[Mechanism] A high baud rate makes each bit interval extremely short, while attenuation and jitter on a long line leave too small a sampling window and cause misjudgment.
[Calculation] At 115200 bps each bit lasts 8.7 μs; over 1200 m the delay jitter exceeds 10% of the bit width and the bit error rate climbs steeply.
[Design Deficiency] The baud rate was not lowered according to distance.
① Baud adaptation: lower the baud rate to match the long line → fewer bit errors
② Distance budgeting: choose the baud-rate limit by distance → keep reliability
③ Repeater segmentation: add repeaters on long runs and raise the rate in segments → combine distance and speed
④ Low-loss cable: choose low-attenuation shielded cable → less loss
⑤ Termination: put termination resistors at both ends → suppress reflection
⑥ Error monitoring: monitor the bit error rate trend and alarm → early detection
⑦ Baud verification: test bit errors at each distance → data confirmation
⑧ Selection standardization: write the baud-rate/distance relationship into the spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification