E45-396 · Communication and Bus · Communication Module · ★★
Ordinary parallel wire is used for communication instead of twisted pair; common-mode rejection is poor and the bit error rate is high
[Mechanism] The absence of twisting in parallel wire gives a large loop area, so external magnetic fields couple asymmetrically and produce differential noise and bit errors.
[Calculation] The loop area of parallel wire is 10 times that of twisted pair; induced noise exceeds the tolerance and the bit error rate rises.
[Design Deficiency] Twisted pair was not used per the bus specification.
① Standard twisted pair: use twisted pair with 120 Ω characteristic impedance → common-mode rejection
② Double-shielded twisted pair: use double-shielded twisted pair in high-interference areas → added shielding
③ Abandon parallel wire: forbid ordinary parallel wire as communication cable → preserve quality
④ Standard lay length: choose cable with a standard twist lay length → suppress coupling
⑤ Single-end shield: ground the shield at one end only → break ground loops
⑥ Cable inspection: check cable types at completion → early correction
⑦ Crosstalk verification: measure bit errors in a noisy environment → data confirmation
⑧ Selection standardization: write communication cable types into the spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification