Incorrect Terminator Resistor Value

E45-397 · Communication and Bus · Communication Module · ★★

Problem Description

The RS485 terminator resistor is mistakenly a value other than 120 Ω, so bit errors persist

Root Cause

[Mechanism] The terminator resistor value does not match the line's characteristic impedance, so the reflection coefficient is not minimized and residual reflections cause bit errors.
[Calculation] Using 220 Ω instead of 120 Ω gives a reflection coefficient of ≈0.29; residual reflections keep the eye diagram from opening fully, causing bit errors.
[Design Deficiency] Termination was not fitted to the 120 Ω standard, and the resistance was not measured.

Corrective Solution

① Standard value: use a precise 120 Ω terminator resistor → match the impedance
② Fit both ends: fit a terminator at each end of the bus, omitting neither → full matching
③ Accuracy selection: choose 1% tolerance resistors → maintain matching
④ Placement at the end: mount right at the bus end of the farthest node → no stub
⑤ Resistance check: measure the resistance before installation → prevent wrong parts
⑥ Reliable soldering: firm solder joints on the resistors → stable contact
⑦ Matching verification: check the eye diagram on an oscilloscope → data confirmation
⑧ Selection standardization: write 120 Ω terminator resistors into the spec → control at the source

Checklist

Reference

GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification