E45-399 · Communication and Bus · Communication Module · ★★
The acquisition bus that requires time synchronization is not synchronized, so timestamps across nodes deviate widely
[Mechanism] Each node's local clock drifts independently and is not aligned, so sampling timestamps use different references and data cannot be aligned.
[Calculation] A crystal drift of 20 ppm causes a 72 ms deviation per hour; the time axes of multiple nodes fall out of step and synchronized sampling fails.
[Design Deficiency] No clock synchronization protocol was enabled, or the master clock was missing.
① Master clock sync: set a master clock and synchronize the whole network → common reference
② Protocol enablement: turn on IEEE1588 time synchronization → correct drift
③ Clock redundancy: hot-standby master clock against failure → keep continuity
④ Drift compensation: compensate the crystal for temperature drift → reduce deviation
⑤ Sync monitoring: alarm when clock deviation exceeds threshold → early detection
⑥ Topology optimization: few hops on the sync path → improve accuracy
⑦ Sync verification: measure time differences across nodes → data confirmation
⑧ Selection standardization: write clock synchronization into the acquisition spec → control at the source
GB/T 25931-2010 Precision clock synchronization protocol for networked measurement and control systems