E45-404 · Communication and Bus · Communication Module · ★★
The Profibus DP bus terminator resistor or baud rate does not match the master configuration, so stations periodically drop off the bus
[Mechanism] The terminator resistor is not correctly switched in or out as each bus segment requires, or the station baud rate differs from the master, so synchronization fails and the station drops off.
[Calculation] One station is set to 1.5 M while the master runs at 12 M; the handshake fails and the station drops off periodically, interrupting communication.
[Design Deficiency] Station parameters were not downloaded uniformly by the master; manual setting is error-prone.
① Uniform download: have the master download station parameters uniformly → prevent misconfiguration
② Terminator switching: switch segment terminator resistors in and out correctly → suppress reflection
③ Consistent baud: use one baud rate across the network → keep synchronization
④ Topology check: check terminators and baud rates at completion → early correction
⑤ Unique station address: assign each station address uniquely → no conflicts
⑥ Drop-off monitoring: monitor periodic station drop-offs and alarm → early detection
⑦ Synchronization verification: measure each station's handshake success rate → data confirmation
⑧ Selection standardization: write Profibus parameters into the configuration spec → control at the source
GB/T 20540.2-2006 Digital data communication for measurement and control - Fieldbus for use in industrial control systems