E45-405 · Communication and Bus · Communication Module · ★★
The outdoor bus cable sheath is damaged and water enters; insulation resistance drops and bit errors worsen with humidity
[Mechanism] Water seeps in along the cable core by capillary action and lowers inter-conductor insulation resistance; leakage current introduces differential noise and causes bit errors.
[Calculation] Water ingress drops inter-conductor insulation from 500 MΩ to 5 MΩ; the leakage current introduces noise beyond the tolerance and the bit error rate rises.
[Design Deficiency] The cable sheath rating was insufficient, or the connectors were not sealed.
① High-protection cable: choose communication cable with a waterproof sheath → block seepage
② Connector sealing: use IP67 sealed connectors → prevent water ingress
③ Drip loops: form drip loops at low points to drain accumulated water → prevent pooling
④ Pressurized maintenance: pressurize critical cables with dry air → block seepage
⑤ Insulation monitoring: monitor inter-conductor insulation and alarm → early detection
⑥ Route away from water: route cables clear of water-collecting trenches → less water ingress
⑦ Water-ingress verification: measure insulation after hot humid conditions → data confirmation
⑧ Selection standardization: write the waterproof rating into the wiring spec → control at the source
GB/T 5023.7-2008 Polyvinyl chloride insulated cables of rated voltages 450-750 V and below