E45-407 · Communication and Bus · Communication Module · ★★★
An internal short in one slave pulls the RS485 bus down; communication is interrupted across all nodes on the network
[Mechanism] A faulty node pulls the bus differential pair to a fixed level; normal nodes can no longer drive the bus and network-wide communication collapses.
[Calculation] The faulty node's output impedance drops toward zero and clamps the bus; normal nodes cannot supply enough drive current and the whole network drops offline.
[Design Deficiency] No node fault isolation or bus protection was provided.
① Fault isolation: add bus fault isolation circuits to slaves → self-disconnect
② Current limiting: add current limiting to transceivers to prevent clamping → protect the bus
③ Optocoupler isolation: isolate each node with optocouplers → no mutual drag-down
④ Node polling: monitor each node's online status and alarm → early detection
⑤ Redundant bus: dual-bus redundancy for critical systems → keep communication running
⑥ Fault location: use diagnostic tools to locate the bad point → fast recovery
⑦ Isolation verification: inject a node short and test the whole network → data confirmation
⑧ Selection standardization: write fault isolation into the network spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification