E45-408 · Communication and Bus · Communication Module · ★★
Neither end of the communication shield is grounded, so external interference has no discharge path and the bit error rate is high
[Mechanism] A floating shield cannot conduct induced current to earth; shielding effectiveness drops sharply and interference couples into the inner conductors.
[Calculation] A floating shield lowers magnetic-field shielding effectiveness by about 20 dB; interference coupling raises the bit error rate compared with single-end grounding.
[Design Deficiency] The shield was mistakenly left ungrounded instead of being single-end grounded.
① Single-end grounding: ground one end of the shield reliably → drain interference
② Solid grounding: remove rust and lower resistance at the grounding point → stable grounding
③ Continuous shielding: keep the shield unbroken over the whole run → preserve effectiveness
④ Dual-shield handling: single-end ground the outer shield of a double shield → add shielding
⑤ Grounding review: measure shield continuity and grounding at completion → early correction
⑥ Interference monitoring: monitor bit error rate and interference → early detection
⑦ Shielding verification: measure bit errors in an interference field → data confirmation
⑧ Selection standardization: write shield grounding into the wiring spec → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields