E45-409 · Communication and Bus · Communication Module · ★★★
The ground potential difference between the two ends of a long line drives the common-mode voltage past the transceiver's limit; communication ports fail in batches with breakdown damage
[Mechanism] The common-mode voltage formed by the potential difference between two grounds exceeds the device's absolute maximum rating; long-term overvoltage ages the transceiver until it breaks down.
[Calculation] A ground potential difference of 15 V exceeds the ±7 V rating; long-term overvoltage sharply shortens transceiver life until breakdown.
[Design Deficiency] Neither wide common-mode nor isolated transceivers were selected.
① Isolated transceivers: use magnetically coupled isolated transceivers → break common-mode
② Wide common-mode: choose ±25 V wide common-mode devices → raise the limit
③ Equipotential bonding: bond the two points → lower the potential difference
④ Single-end grounding: ground the shield at one end → break the circulating loop
⑤ Floating layout: leave remote devices floating → avoid ground difference
⑥ Potential monitoring: monitor common-mode voltage and alarm → early detection
⑦ Common-mode verification: apply common-mode voltage and test service life → data confirmation
⑧ Selection standardization: write the common-mode range into the selection criteria → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields