E45-411 · Communication and Bus · Communication Module · ★★
The communication ground is tied directly to the power ground; high-current ground noise from the inverter bleeds into the communication link and causes bit errors
[Mechanism] Large currents in the power ground generate ground noise; once the grounds are tied together this noise superimposes on the communication ground and drifts the differential reference.
[Calculation] Power-ground noise reaches hundreds of mV and couples through the shared connection, pushing communication common-mode noise past the tolerance and causing bit errors.
[Design Deficiency] Strong- and weak-current grounds were not separated and single-point connected.
① Separate grounds: run communication and power grounds separately → avoid noise bleed
② Single-point common connection: tie the two grounds at one point only → control noise
③ Isolated transceivers: use isolated transceivers to break ground coupling → resist noise
④ Ferrite bead isolation: insert a ferrite bead at the common point to suppress high frequency → lower coupling
⑤ Ground-noise monitoring: monitor communication ground noise and alarm → early detection
⑥ Grounding review: check the grounding topology at completion → early correction
⑦ Mixed-ground verification: measure ground noise and bit errors → data confirmation
⑧ Selection standardization: write grounding zoning into the grounding spec → control at the source
GB/T 50065-2011 Code for design of grounding for AC electrical installations