E45-412 · Communication and Bus · Communication Module · ★★
Very long RS485 buses have large distributed capacitance; the slowed signal rise edges cause bit errors in high-speed communication
[Mechanism] The distributed capacitance of the long line forms an RC circuit with the load, slowing the signal edges so they are not settled within the sampling window and errors occur.
[Calculation] A bus capacitance of 2 nF with the 120 Ω termination gives a time constant that makes the edge exceed the bit width by 30%, causing bit errors.
[Design Deficiency] No baud rate reduction or added drive was applied for the high-speed long line.
① Lower baud rate: reduce the baud rate on long lines to match the capacitance → stabilize edges
② Strong drive: choose high-drive transceivers → fast edges
③ Repeater segmentation: add repeaters on long lines to cut segment capacitance → reduce RC
④ Low-capacitance cable: choose low-capacitance communication cable → slow the edge less
⑤ Termination: put termination resistors at both ends → suppress reflection
⑥ Edge review: check the edge time with an oscilloscope → early correction
⑦ Capacitance verification: measure edges and bit errors → data confirmation
⑧ Selection standardization: write distributed capacitance into the design checklist → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification