E45-418 · Communication and Bus · Communication Module · ★★
The RS485 bus has a termination resistor at only one end; the open end causes partial reflection and bit errors at the far end
[Mechanism] Matching at only one end leaves the other end impedance-mismatched and produces reflection; the partial reflection superimposes and distorts the far-end waveform into bit errors.
[Calculation] With 120 Ω at one end and an open circuit at the other, the reflection coefficient is about 0.5, half-closing the eye diagram and raising the bit error rate.
[Design Deficiency] The far-end node had no terminator, or it was omitted.
① Terminate both ends: fit a termination resistor at each end of the bus → full matching
② End verification: the farthest node end must have a terminator → eliminate open circuits
③ Terminator marking: mark where terminators are installed to prevent omission → prevent errors
④ Resistance check: measure the 120 Ω value accurately before installation → ensure matching
⑤ Topology review: check the terminators at both ends at completion → early correction
⑥ Reflection monitoring: monitor far-end bit errors and alarm → early detection
⑦ Partial reflection verification: check the far-end eye diagram with an oscilloscope → data confirmation
⑧ Selection standardization: write both-end termination into the spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification