E45-419 · Communication and Bus · Communication Module · ★★
A custom multi-master RS485 has no arbitration; two masters transmit frames at the same time and they collide, blocking the bus for a long time
[Mechanism] A half-duplex multi-master bus has no carrier sensing or arbitration; simultaneous transmission makes frames collide and occupies the whole bus.
[Calculation] Two masters transmitting at once keep colliding until bus occupancy times out; normal communication stalls.
[Design Deficiency] The multi-master protocol implemented neither CSMA/CD nor a master token.
① Token arbitration: switch multi-master to token-ring controlled transmission → no collisions
② Carrier sensing: listen for an idle bus before transmitting → avoid collisions
③ Master-slave redesign: change to a single-master multi-slave structure → avoid contention
④ Backoff retransmission: back off randomly and retransmit after a collision → reduce congestion
⑤ Timeout release: force release when occupancy times out → keep the bus clear
⑥ Conflict monitoring: monitor bus utilization and alarm → early detection
⑦ Conflict verification: transmit from two masters at once and measure the blockage → data confirmation
⑧ Selection standardization: write multi-master arbitration into the protocol spec → control at the source
GB/T 19582.1-2008 Modbus protocol-based industrial automation network specification