E46-410 · Commissioning & Run-In · Fan bearing · ★★
The fan test run only checked that the speed met target without measuring bearing vibration; a month later the vibration velocity reached 11mm/s and the bearing cage fractured.
[Mechanism] Early unbalance or looseness makes vibration creep up, and without monitoring the fatigue spreads.
[Calculation] An RMS vibration velocity above 7.1mm/s is the unacceptable zone and accelerates damage.
[Design gap] Vibration was not made a mandatory test-run item.
① Always measure vibration: measure the RMS bearing vibration velocity throughout the test run and investigate above 4.5mm/s
② Spectrum analysis: use spectra to see whether it is unbalance or misalignment and locate the source
③ Dynamic balancing: if out of tolerance, dynamically balance the impeller before retesting
④ Tighten anchor bolts: check the anchor and connecting bolts for tightness and eliminate the source of looseness
⑤ Measure at several speeds: measure vibration at multiple speed points and avoid the resonance zone
⑥ Trend log: record the vibration trend and warn when the threshold is exceeded
⑦ Quality verification: confirm acceptance by vibration value and spectrum, confirmed by data
⑧ Standardize process: write vibration measurement into the test-run card, controlling at the source
GB/T 6075.1-2012 Mechanical vibration - Measurement and evaluation of machine vibration on non-rotating parts