E46-433 · Commissioning & Run-In · VFD-driven motor · ★★★
The VFD was run on factory defaults straight onto the motor, with no motor rated parameters or acceleration/deceleration settings, and it tripped on overcurrent at start-up.
[Mechanism] Wrong parameters leave the output frequency and current mismatched, and the starting torque runs out of control.
[Calculation] Too short an acceleration time pushes the starting current to twice rated, tripping the breaker.
[Design gap] The parameters were not set from the motor nameplate.
① Enter nameplate: input the motor's rated power, voltage, current and pole number
② Set accel/decel: set the acceleration and deceleration times for the load to avoid overcurrent
③ V/f ratio: set the rated voltage-to-frequency ratio to preserve torque
④ Limit current: set the electronic thermal relay and the current limit
⑤ Jog: jog at low frequency first to check the rotation direction and current
⑥ Record: record the parameters and the trip values
⑦ Quality verification: confirm acceptance by running current and no tripping, confirmed by data
⑧ Standardize process: write parameter setting into VFD commissioning, controlling at the source
GB/T 12668.2-2012 Adjustable speed electrical power drive systems