E46-439 · Commissioning & Run-In · Automated production line · ★★★
The electrical signal acted before the mechanism was in position, so the gripper released before the workpiece was clamped and the workpiece flew out and damaged the equipment.
[Mechanism] The action is executed before the interlock conditions are satisfied, so the sequence is reversed.
[Calculation] A missing clamped signal raises the probability of a wrong action, causing a collision with the workpiece.
[Design gap] No sequence simulation or interlocking was done for the linked motions.
① Interlock: make the clamped-in-position signal a precondition for releasing
② Simulate: run a sequence simulation before commissioning to check the logic
③ Single step: confirm the sequence in single-step mode before linked motion
④ Sensors: calibrate the position sensors so that they are valid and the signals are true
⑤ Emergency stop: the emergency stop works during linked motion and cuts off immediately on any abnormality
⑥ Record: record the linked-motion steps and the interlock points
⑦ Quality verification: confirm acceptance by sequence and interlocks, confirmed by data
⑧ Standardize process: write the linked-motion sequence into the control program, controlling at the source
GB/T 5226.1-2019 Electrical safety of machinery - Electrical equipment of machines - Part 1