E41-059 · Motor Selection · High-Altitude Mine Conveyor · ★★★
A motor used at a mine 3800m above sea level burned out its stator winding after three months of service. The insulation resistance fell to zero, and the temperature recorder showed the motor running at 135℃ (Class F insulation permits 155℃) while the ambient temperature was only 5℃.
The altitude correction factor was not considered at selection. The motor's rated power is 110kW (rated at altitudes up to 1000m) while the operating site is 3800m. According to GB/T 755, for every 100m of altitude increase the motor temperature rise increases by 1% and the cooling efficiency drops by 1%. At 3800m the correction factor is K=1+(3800-1000)/1000×0.01=1.028, so the actual power must be derated to 110×0.972=107kW. But the actual load power is 108kW, already close to the derated limit. In addition the thin high-altitude air (density only 65% of sea level) reduces the airflow of the motor's own cooling fan by 35%, further degrading cooling efficiency. The combined temperature rise is 80K rated ×1.028×1.35≈111K; adding the 5℃ ambient gives a winding temperature of 116℃, which appears to be within the Class F range, but the 108kW load already exceeds the derated 107kW, and the actual airflow is lower than the theoretical value, so the final actual temperature rise is about 130K with a winding temperature of 135℃, accelerating insulation ageing.
1) Altitude correction: derate by 8~10% per 1000m, or apply an ambient temperature compensation of -5℃/1000m
2) At 3800m derate to 110×0.76=83.6kW (based on 8% derating per 1000m)
3) If derating is not accepted, redesign with a larger frame (e.g. from the 110kW frame to the 160kW frame)
4) Use a high-altitude special motor: larger fan diameter (airflow increased by 30%), Class F insulation with Class H temperature rise assessment
5) Add auxiliary cooling: an independent fan (not self-ventilated) plus an intercooler
6) Note: at high altitude the corona ageing of the motor insulation must also be considered (thin air lowers the corona inception voltage)
FT_12_Motor Selection Systematization