E41-161 · Motor Selection · Continuous Running Conveyor Line Drive Motor · ★★★★
After one year of continuous running the conveyor motor tripped out frequently on overload, and the motor casing reached 95℃ (80℃ permitted). Teardown showed the stator winding insulation aged and embrittled with the enamelled wire discoloured.
The motor rated power is 7.5kW while the actual load is 7.2kW, a load factor of 96% and a safety factor of only 1.04 (≥1.2 recommended). Running for long periods close to rated power gives a winding temperature rise θ=(P_load/P_rated)²×θ_rated=0.96²×80=73.7K. With an ambient temperature of 35℃ the winding reaches 35+73.7=108.7℃. Class B insulation (130℃) appears safe, but under the fluctuating conveyor load the peak power reaches 8.5kW (13% short-time overload) and the peak temperature reaches 120℃. By the Arrhenius relationship the insulation life halves for every 10℃ rise, so one year at 120℃ is equivalent to about three years at rated temperature rise, shortening the insulation life by about 67%.
1) Motor power selection safety factor ≥1.2 (≥1.3 for continuous running)
2) An upgrade is needed here: 7.5kW→11kW (load factor down to 65%)
3) Select a Class F insulation motor (permitted temperature rise 105K, more resistant to high temperature)
4) Add motor temperature monitoring (PT100 resistance thermometer embedded in the winding)
5) Periodically test the insulation resistance (every 3 months, ≥0.5MΩ/kV)
FT_12_Motor Selection Systematization