E41-173 · Motor Selection · Long-Running Fan Motor · ★★★
The fan motor was specified as an IE2 standard-efficiency motor (efficiency 89.5%), running 8000h per year at an electricity price of 0.8 CNY/kWh, so the annual electricity cost is about 228,000 CNY. No economic comparison was made against an IE4 ultra-high-efficiency motor (efficiency 95.5%).
The motor is 75kW running 8000h per year with an efficiency difference Δη=6%. The annual extra energy consumption is E_loss=75×8000×0.06=36000kWh, giving an electricity cost difference of 36000×0.8=28800 CNY per year. The IE4 motor costs about 20,000 CNY more, so the payback period is 20000/28800=0.69 years ≈ 8.3 months. With a motor life of 15 years the life-cycle saving is 28800×14.3 (deducting the 0.69-year payback) ≈ 412,000 CNY. Because this analysis was not carried out an IE2 motor was selected, costing about 410,000 CNY more in electricity over 15 years.
1) Motors that run for long periods (over 4000h per year) require an LCC life-cycle cost analysis
2) LCC=initial investment+Σ(annual electricity cost + maintenance cost)/(1+r)^n
3) In this case the IE4 option saves 410,000 CNY over 15 years, so IE4 should be preferred
4) IE4 motor efficiency 95.5% against IE2 89.5%, an efficiency difference of 6%
5) High-efficiency motors also give additional benefits: lower temperature rise (extending insulation life) and fewer failures
FT_12_Motor Selection Systematization