E41-336 · Motor Selection · Second-hand Equipment Motor Selection · ★★★
When second-hand equipment was purchased the motor nameplate read 55kW, but on trial running after installation the motor tripped on overload. Measurement showed the rated current was only 95A (corresponding to 45kW): the nameplate had been altered.
The seller of the second-hand equipment replaced the nameplate of a 45kW motor with a 55kW nameplate (the current changed from 85A to 105A). The buyer selected the cable (3×35mm²), the circuit breaker (125A) and the contactor (125A) on the basis of 55kW. The actual motor is 45kW with a rated current of 85A, so driving a 55kW load overloads it by 29%. Running in this overloaded state the current was 105A (the nameplate value), already 23% above the actual rated current of 85A, and the winding temperature rise θ=(I_actual/I_rated)²×θ_rated=(105/85)²×80≈122K, giving a winding temperature of 30+122=152℃, far above Class B insulation (130℃). The thermal relay tripped after 10 minutes.
1) The nameplate parameters of a second-hand motor should be re-verified (measure the stator resistance and the no-load current to deduce the actual power)
2) Compare the motor frame dimensions: motors of the same power rating should have identical overall dimensions
3) Measure the motor shaft extension diameter: the standard dimensions for a given power can be looked up
4) Judge by the motor center height: H280 corresponds to 55kW and H250 to 45kW
5) The most reliable method is a no-load test (measuring the no-load current and iron loss to judge the actual power)