E41-477 · Motor Selection · High-Power Inverter Motor Shaft Current · ★★★★
One year after the 250kW inverter motor started running the bearings showed electrical erosion, with washboard-like discharge streaks on the raceway surface. No common-mode reactor had been installed at the inverter output.
The inverter PWM output generates a common-mode voltage (about 500V) which couples to the rotor through the distributed capacitance (about 10nF) between the stator winding and the rotor. The voltage between the shaft and the bearing is U_shaft=U_CM×C_wr/(C_wr+C_b)≈500×10/(10+1)≈455V. When the shaft voltage exceeds the bearing oil film breakdown voltage (about 1~5V), spark discharge occurs. The discharge energy is E=½C_b×U²=0.5×1×10⁻⁹×455²≈0.1mJ, forming tiny discharge pits on the raceway surface (about 5μm in diameter). Roughly 100 discharges occur each second (the PWM carrier frequency is 2kHz and each pulse group produces one discharge), giving about 360,000 discharges in one hour and about 3×10⁹ in one year. Under countless discharge pits the raceway surface develops a washboard-like pattern and the vibration value rises from 2mm/s to 10mm/s.
1) High-power inverter motors (>100kW) must have an output common-mode reactor fitted (to suppress common-mode current)
2) Select insulated bearings (ceramic rollers or an insulating coating) for the non-drive-end bearing
3) Fit a shaft grounding brush at the drive end (earthing the shaft voltage directly, ≤0.5V)
4) Raise the inverter carrier frequency above 4kHz (the common-mode voltage amplitude falls by about 20%)
5) Use conductive grease (lowers the bearing resistance and prevents charge accumulation)