E41-486 · Motor Selection · Intermittent-Operation Winding Moisture · ★★★
A pump motor (30 kW) operating intermittently in a humid environment (2 h running, 22 h stopped per day) saw its insulation resistance drop from 500 MΩ to 0.5 MΩ within 6 months.
During the shutdown period (22 h/day), the winding temperature drops to ambient (about 30℃) with an environmental humidity of 85%. The residual moist air inside the motor condenses on the winding surface under water-vapor partial pressure (dew condensation), forming a thin water film. The insulating material (polyester enameled wire + insulating varnish) absorbs moisture and its resistance drops. During the 22 h shutdown the winding surface dew-condenses; during the 2 h running the winding temperature rises (about 90℃) and evaporates the moisture. But the 22 h daily condensation time exceeds the 2 h drying time, so moisture accumulates day by day in the insulation. After 6 months the insulation resistance falls from 500 MΩ to 0.5 MΩ (a 99.9% drop). Too-low insulation resistance can cause a ground fault when starting the motor.
① Add an offline heating strip to the intermittent motor (50~100 W, keep winding temperature 5~10℃ above ambient)\n② Fit a moisture-proof cover (rain shield + bottom vents to reduce water ingress)\n③ Place desiccant inside the motor (silica gel bag, replaced every 6 months)\n④ Check insulation resistance before restarting (≥1 MΩ/kV)\n⑤ If insulation is substandard, perform drying (hot-air / short-circuit-current drying)
FT_12 Systematic Motor Selection