E41-487 · Motor Selection · Motor Overload Protection Curve Mismatch · ★★★★
A motor with frequent starting (4 times per minute) was protected by an ordinary thermal relay, which mis-tripped during normal starts, preventing normal production.
The motor rated current is 85 A; during frequent starting the starting current I_st = 6 × 85 = 510 A for 0.5 s (no-load start). The thermal relay (set at 85 A) has an operating time of about 2 s at 510 A (per its characteristic curve), and the 0.5 s start time < 2 s means it should not trip in theory. But frequent starting (4 times per minute, ~2000 times per day) causes the bimetallic strip to accumulate heat under repeated heating, and its temperature keeps rising. After about 30 consecutive starts the strip reaches the trip threshold and the relay opens (nuisance trip). The motor is actually not overloaded (starting current is normal), yet the frequent relay tripping prevents continuous production.
① Use an electronic overload relay for frequent-starting motors (with thermal memory, distinguishing starting current from overload current)\n② Electronic relays can auto-adjust the trip threshold by starting frequency\n③ Or use PTC protection (directly senses winding temperature, unaffected by starting current)\n④ Raise the thermal relay setting to 1.05 × I_n (89 A) to reduce nuisance trips on frequent starts\n⑤ Or use a current transformer + PLC protection (programmable trip curve)