MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Selection Error Cases › Insufficient torque due to excessive motor supply-voltage fluctuation (remote-area supply)

Insufficient torque due to excessive motor supply-voltage fluctuation (remote-area supply)

E41-489 · Motor Selection · Motor Voltage-Fluctuation Torque Shortage · ★★★

Problem Description

A motor (75 kW) in a remote area had difficulty starting when voltage dropped to 320 V (no-load start needed 15 s to reach rated speed; full-load start impossible).

Root Cause

The motor rated voltage is 380 V; supply dropped to 320 V (down 15.8%). For an induction motor the starting torque T_st ∝ U²; at 320 V, T_st = K × U² = K × 320² = K × 102400, while at rated it is K × 380² = K × 144400, so starting torque falls to 102400/144400 = 0.709 (70.9%) of rated. Rated starting torque is 1.8× the rated torque, dropping to 1.8 × 0.709 = 1.28×. At full-load start the load torque is 1.0× rated; 1.28 > 1.0, so it can start but the start time lengthens (T_acc = (T_st − T_load)/J). No-load start time extends from 3 s to 15 s; full-load start time is about 40 s (exceeding the motor's allowed start time of 30 s), and the rotor sits at starting current (~400 A) for 40 s. Heat rise θ = I² × R × t / (m × c) = 400² × 0.02 × 40 / (30 × 400) ≈ 10.7 K; with rated-current heating added, cumulative rise is about 70 K, shortening insulation life under high temperature.

Corrective Solution

① Allowable supply-voltage fluctuation range: ±10% (342~418 V)\n② When drop > 10%, install a voltage stabilizer (AC regulator or voltage adjuster)\n③ Or use a VFD (has voltage-boost function to raise starting torque at low voltage)\n④ Change starting method to star-delta / soft start (reduce starting current and grid-voltage impact)\n⑤ Equip reactive-power compensation (raise power factor, reduce line drop)

Checklist

Reference

FT_12 Systematic Motor Selection

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL