E41-490 · Motor Selection · Motor Repair Thinner Winding Wire · ★★★
A motor (30 kW) after repair ran with normal current but high temperature rise (80 K vs. allowed 75 K); during repair the original winding wire diameter Φ1.25 mm was changed to Φ1.12 mm.
During repair the shop, to cut cost, changed the original winding wire from Φ1.25 mm to Φ1.12 mm (cross-section from 1.227 mm² down to 0.985 mm², a 19.7% reduction). Winding resistance R = ρ × L / A; after a 19.7% smaller diameter the resistance rises to 1.227/0.985 = 1.246× (a 24.6% increase). Copper loss P_cu = I² × R; at the same current (rated 57 A), copper loss rises 24.6%, from about 3.2 kW to about 4.0 kW (R in I²R increases 24.6%). Winding temperature θ = θ_ambient + P_cu × R_th = 40 + 4000 × 0.02 = 120℃ (R_th = thermal resistance ≈ 0.02 K/W). Actual temperature = 40 + 80 = 120℃, above the B-class insulation limit of 130℃, but the 80 K rise already exceeds the standard 75 K. Long-term high-temperature operation accelerates insulation aging, cutting motor life from 20 years to about 3 years.
① Motor repair must restore the original winding parameters (wire diameter / turns / pitch); no unauthorized changes\n② Perform a no-load test after repair (no-load current should be ≤ 30% of rated)\n③ Perform a temperature-rise test after repair (run 4 h at rated load; rise ≤ standard)\n④ Use a reputable motor-repair shop (require repair records and test reports)\n⑤ Record repair parameters after repair (archive for reference and checking at next repair)