E41-495 · Motor Selection · Outdoor Explosion-Proof Motor Water Ingress · ★★★★
An outdoor explosion-proof motor (ExdⅡBT4) tripped on ground fault after a heavy rain; teardown found water pooled inside the junction box and insulation resistance at zero. The explosion-proof junction-box gasket (NBR) had aged and failed.
Between the explosion-proof junction-box cover and body sits an NBR (nitrile rubber) gasket (3 mm thick, Shore A 70 hardness). After 3 years outdoors, the NBR aged and cracked under ultraviolet (sun) and ozone exposure (surface cracks about 1 mm deep). During heavy rain, water entered the junction box through the cracked gasket (about 50 ml pooled). The motor terminals were submerged; insulation resistance dropped from 500 MΩ to 0 Ω (ions in water conduct). Energizing caused a ground-fault trip. In an explosion-proof motor, gasket aging is not only a waterproofing issue but also a flameproof-integrity risk in hazardous areas (failure of the Exd flameproof joints).
① For outdoor explosion-proof motors, change gasket material: NBR → silicone rubber (ozone/UV resistant, 5-year life)\n② Replace gaskets periodically: NBR every 2 years / silicone every 4 years\n③ Use a torque wrench on junction-box bolts (ensure even gasket compression)\n④ Fit a rain shield over the junction box (stainless steel, blocks direct rain)\n⑤ Place desiccant inside the explosion-proof junction box (silica gel bag, replaced every 6 months)
FT_12 Systematic Motor Selection