Knowledge Base › Selection Error Cases › Sensor Temperature Drift Causing Measurement Error in High-Temperature Environment (Workpiece Position Detection Inside Heat-Treatment Furnace

Sensor Temperature Drift Causing Measurement Error in High-Temperature Environment (Workpiece Position Detection Inside Heat-Treatment Furnace)

E41-049 · Sensor Electrical Selection · Workpiece Position Detection Inside Heat-Treatment Furnace · ★★★

Problem Description

During heating from room temperature to 800℃, the position sensor signal drifts about 5 mm, causing the robot gripper to fail and the workpiece to fall into the furnace.

Root Cause

A standard inductive proximity switch with an operating temperature range of 0~70℃ was selected. During heating, radiant and conductive heat inside the furnace raised the sensor mounting location (furnace wall exterior) to 120℃, far exceeding the sensor's upper operating-temperature limit. The sensor's internal electronics (oscillator, signal-processing circuit) suffered severe drift at 120℃: oscillator-frequency drift changed the detection distance (from 10 mm to 15 mm) and the altered trigger threshold caused incorrect output logic. The electronics also risked irreversible damage from overheating.

Corrective Solution

① The sensor operating temperature must cover the actual mounting-location temperature (with 20℃ margin)
② In this case the mounting location reaches 120℃ → select a sensor rated above 150℃
③ Option A: high-temperature inductive sensor such as Turck Ni15-M30-AZ3X (operating temperature −40~160℃ ✓)
④ Option B: fiber-optic sensor with remote fiber probe (electronics kept away from heat source; fiber probe rated to 250℃)
⑤ Option C: install a water jacket (stainless-steel cooling jacket with cooling water at 0.5~1 L/min, lowering the sensor mounting temperature by 40~60℃)
⑥ Add a heat shield (ceramic-fiber board, 10 mm thick) to reduce thermal radiation, lowering temperature by 20~30℃
⑦ Key point: all options must be verified by actual temperature measurement at the sensor mounting location to confirm it stays within the allowable range

Checklist

Reference

FT_33_Sensor Selection Guide

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »