Knowledge Base › Selection Error Cases › Proximity-Switch Detection-Distance Temperature Drift Causing False Trips (Hot-Rolled Slab Tracking)

Proximity-Switch Detection-Distance Temperature Drift Causing False Trips (Hot-Rolled Slab Tracking)

E41-106 · Sensor Electrical Selection · Hot-Rolling Line Slab Tracking · ★★★

Problem Description

When the hot-rolled slab temperature reaches 800℃, the proximity-switch detection distance drifts from 15 mm to 25 mm, expanding the detection range and causing false trips; the system misjudges the slab position.

Root Cause

A standard M30 inductive proximity switch (detection distance 15 mm) with operating temperature −25~70℃ was selected. However, the mounting position is only 200 mm from the hot slab, and thermal radiation raises the sensor head temperature above 150℃. The temperature-drift coefficients of the inductor coil and capacitor in the sensor's internal oscillator circuit are about 500 ppm/K; at a 125℃ temperature rise (25→150℃) the oscillation frequency shifts by 6.25%. Meanwhile the coil resistance increases (copper wire temperature coefficient +0.4%/K) and oscillator gain drops. The combined effect drifts the detection distance from 15 mm to 25 mm (67% drift). With a fixed threshold comparison in the PLC program, the false-trip rate reached 30%.

Corrective Solution

① Sensors in thermal environments should be high-temperature-rated (operating temperature ≥120℃)
② Recommended: high-temperature inductive sensor (e.g., Turck Ni15-M30-AZ3X, −40~160℃)
③ Add a heat shield (10 mm ceramic fiber plus stainless-steel air gap) to lower sensor temperature
④ Use dynamic-threshold compensation in the PLC program (correct the detection threshold based on ambient temperature)
⑤ Or switch to a photoelectric sensor (mount away from the heat source; fiber probe rated to 250℃)

Checklist

Reference