E41-294 · Sensor Electrical Selection · Sensor-Cable Interference · ★★★★
The 4~20mA pressure transmitter signal measures 3.5~4.5mA fluctuation at the PLC end (should be 12mA steady), with more severe fluctuation when the motor starts.
The pressure transmitter cable (2-core shielded, 0.5mm²) and the VFD power cable (3×16mm²) are laid side by side in the same cable tray with 0mm spacing (in direct contact). The VFD carrier frequency is 4kHz, PWM output current slew rate di/dt ≈ 2000A/μs, generating a strong electromagnetic field around the power cable. Electromagnetic coupling induces a common-mode voltage in the signal cable U_cm = M×di/dt = 0.1μH × 2000A/μs = 0.2V. For a 4~20mA signal (1~5V at 250Ω load), 0.2V common-mode interference causes about 0.8mA signal-current fluctuation. The shield is grounded only at the PLC end (single-ended), so high-frequency interference returns to the sensor end through distributed capacitance, forming a loop.
① Signal cable and power cable spacing ≥300mm; never lay in the same cable tray\n② Signal cable uses twisted-pair shielded cable (twist pitch ≤25mm, 10× better interference rejection than ordinary shielding)\n③ Shield grounded at both ends (signal end + PLC end, grounding impedance ≤4Ω)\n④ Add an isolator to PLC analog input (magnetic/optical isolation, common-mode rejection ≥120dB)\n⑤ Add a ferrite core to the signal wire (3 turns at the PLC input)