E41-466 · Other Selection · Boiler Level Gauge Glass Rupture · ★★★★★
The glass plate (mica sheet + tempered glass composite) of a boiler drum level gauge suddenly ruptured during operation; high-temperature steam (250 ℃, 4.0 MPa) jetted out, injuring personnel.
The boiler level gauge glass plate (tempered glass, 8 mm thick) operates under high temperature and pressure (250 ℃, 4.0 MPa) and thermal shock (especially when feeding water to the boiler, temperature difference about 100 ℃). Under 100 ℃ thermal shock the tempered glass develops thermal stress σ_th = E×α×ΔT = 72000×8.5×10⁻⁶×100 ≈ 61.2 MPa (E = 72 GPa, α = 8.5×10⁻⁶/℃). The tempered glass surface pre-stress is about 90 MPa; the 61.2 MPa thermal stress brings surface tensile stress close to the glass tensile strength (about 100 MPa). The gasket (graphite) compresses unevenly with each thermal shock, and frame bolts have uneven preload (wrong diagonal tightening sequence), causing local stress concentration in the glass. After about 200 thermal-shock cycles, cracks initiate at the stress-concentration region and propagate until the glass plate ruptures.
① Use mica sheets for the boiler level gauge (natural mica, temperature resistance 800 ℃, far better thermal-shock resistance than glass).\n② Tighten the level gauge frame bolts diagonally with a torque wrench (M12, torque 60 Nm).\n③ Operate boiler feed water slowly (control feed rate to reduce thermal shock).\n④ Fit a protective cover on the level gauge (tempered glass + stainless steel mesh, to prevent fragment splashing).\n⑤ Replace the level gauge periodically (annually, or immediately on finding cracks).
FT_Machine Design Handbook