E41-751 · Other Selection Topics · Cooling Tower Fan Pulley Speed · ★★★
After a cooling tower fan pulley (the driven pulley) was replaced (outside diameter Φ450mm), the fan speed fell from 250r/min to 200r/min and the air flow dropped by 20%.
The motor runs at 1450r/min, the driving pulley is Φ200mm and the driven pulley was originally Φ360mm but was replaced by a new Φ450mm (a machining dimension error). The theoretical speed is n₂=n₁×D₁/D₂=1450×200/360=805rpm; with the actual values the original speed was n₂=1450×200/360=805rpm and after the replacement n₂=1450×200/450=644rpm. Cooling tower fan speeds are typically a few hundred r/min and the belt drive provides a step-down ratio. With the original driven pulley of Φ360mm the ratio is i=360/200=1.8 and the fan speed n₂=1450/1.8=805rpm. With the new Φ450mm pulley, i=450/200=2.25 and n₂=1450/2.25=644rpm. The fan air flow is proportional to speed: Q₂=Q₁×n₂/n₁=100%×644/805=80%, so the flow fell by 20% and the cooling performance was inadequate. The error arose because the maintenance worker did not check the driven pulley dimension and fitted a wrongly sized pulley taken from the store.
1) Re-check all the parameters against the correct selection specification;
2) Confirm that the duty load, environment and life all meet the design requirements;
3) Select a reliable brand and a suitable model;
4) Verify the installation and operating conditions;
5) Inspect and maintain the equipment at regular intervals after commissioning.