E41-805 · Other Selection · Cooling Pipe Scaling · ★★★★
After 1 year of operation, the equipment cooling water system's cooling effect declined; the cooling water temperature rise went from 5 °C to 15 °C, and the equipment frequently alarmed for overheating.
The cooling water was untreated well water (hardness about 300 mg/L as CaCO₃), which formed scale (CaCO₃, thermal conductivity about 2 W/m·K) on the water side of the heat exchanger (plate heat exchanger, 316L, heat-transfer area 10 m²). After 1 mm of scale, the overall heat-transfer coefficient of the exchanger dropped from 3000 W/m²·K to 1800 W/m²·K (a 40% drop), and cooling capacity from 30 kW to 18 kW. Scaling also narrowed the water channel (plate gap from 2 mm to 1.5 mm), reducing flow from 8 m³/h to 5 m³/h and further lowering heat-exchange efficiency. After 1 year the cooling capacity was only 12 kW, less than 50% of the demand (25 kW).
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning
FT_Machine Design Handbook