Overpressure Due to Improper Safety Valve Selection in Pneumatic System

E41-710 · Pneumatic Component Selection · Pneumatic Safety Valve · ★★★★

Problem Description

Air receiver pressure rose to 1.1 MPa (design 0.88 MPa), and the safety valve did not open.

Root Cause

Spring stress relaxation made the set pressure drift from 0.85 to 1.0 MPa, and the valve disc rusted and stuck.

Corrective Solution

① Calibrate the safety valve once a year
② Calibrate set pressure before installation
③ Install an electric-contact pressure gauge on the air receiver for overpressure shutdown

Checklist

Reference