E42-178 · Corrosion Failure · Brass Gate Valve DN100 · ★★★
Valve body surface powdered, ruptured and leaked during the hydrostatic test.
[Dezincification] In seawater, the β phase of α+β brass dissolved preferentially, dezincified layer 2mm deep. [Strength Drop] Remaining porous α phase lost 60% strength. [Design Omission] No naval brass and no coating; rupture and water leakage.
1. Change to naval brass HSn62-1.
2. Apply an epoxy coating on the valve body surface.
3. Add cathodic protection in the dezincification-sensitive zone.
4. Control medium flow velocity ≤2m/s.
5. Add corrosion inhibitor to the medium.
6. Add 2mm corrosion allowance to the wall thickness.
7. Regular thickness measurement.
8. Increase hydrostatic test to 1.5 times.
GB/T 10125-2021