E42-179 · Corrosion Failure · Chemical Globe Valve · ★★
Valve seat seal surface pitted 0.5mm deep, internal leakage.
[Wear Corrosion] Medium contains solid particles, erosion and corrosion acted synergistically, seal surface lost luster and pitted. [Internal Leakage] Line seal destroyed, leakage exceeded the limit. [Design Omission] No hard alloy surfacing and no flow velocity control; internal leakage.
1. Surface-weld hard alloy Stellite on the valve seat.
2. Control medium flow velocity ≤3m/s.
3. Add a filter upstream.
4. Lap the seal surface to Ra0.4.
5. Add cathodic protection.
6. Regularly lap the seal surface.
7. Add corrosion inhibitor to the medium.
8. Online monitoring of internal leakage.
GB/T 12224-2015